How many auxiliary switches can be put in a Powerpact H or J Frame breaker?
Issue:
How many auxiliary switches can be put in a Powerpact H or J Frame breaker?
Product Line:
Circuit Breakers
Environment:
Powerpact H and J breakers
Resolution:
For a 3-pole breaker:
One or 2 auxiliary switch accessories can be added. Each is a 1A1B form C contact. This gives total 2A2B.
In addition, these breakers will accept one SD (alarm) switch and one SDE (overcurrent trip alarm) switch.
NOTE: Installation of an SDx, NSX cord, BSCM, 24 Vdc Supply Terminal Block, or SDTAM accessory will affect the number of switches that can be installed. See attachment for details.
An HD or HG 2-pole breaker will accept only one aux switch and one SD alarm switch. An SDE is not possible.
How many auxiliary switches can be put in a Powerpact H or J Frame breaker?
Product Line:
Circuit Breakers
Environment:
Powerpact H and J breakers
Resolution:
For a 3-pole breaker:
One or 2 auxiliary switch accessories can be added. Each is a 1A1B form C contact. This gives total 2A2B.
In addition, these breakers will accept one SD (alarm) switch and one SDE (overcurrent trip alarm) switch.
NOTE: Installation of an SDx, NSX cord, BSCM, 24 Vdc Supply Terminal Block, or SDTAM accessory will affect the number of switches that can be installed. See attachment for details.
An HD or HG 2-pole breaker will accept only one aux switch and one SD alarm switch. An SDE is not possible.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.