How can we help you today?

Can the Class 9422 Type TF1 non-fusible disconnect switch be converted to Class 9422 Type TF2 200 amp fusible switch?

Issue:
Convertion of 9422TF1 to 9422TF2

Product Line:
Operating Mechanisms and Disconnect Switches

Environment:
North American Products

Resolution:
Yes, order 40512-363-50 switch base assembly and 31055-363-50 fuse base assembly.
Note the fuse base is complete but the switchbase does not include lugs so existing line side lugs must be used with new switch base.