How can you connect the #12 leads (20 Amp.) because of the wire size on the SDSB1175C (Surgebreaker Plus) Whole House Surge Protector to a 30 Amp. Breaker?
The leads are tested at the 30 Amp. rating and are UL listed for this application. This is because there is no continuous current being drawn when the unit is connected.