Which wire should be removed from Class 8536 Type S starter to configure for separate source control?

Issue:
What wire should be removed from Class 8536 Type S starter to configure for separate source control?

Product Line:
Nema and Definite Purpose Contactors and Starters

Environment:
North American Products

Cause:
Needs the know Which wire should be removed from Class 8536 Type S starter to configure for separate source control.

Resolution:
Remove jumper wire between terminal L2 of contactor and ``COM`` terminal on overload relay contact module. This applies to size 00 through size 5 only. For conversion of size 6 or 7 consult Marketing Product Support Group.