What is the proper lubricating grease required for the QMB switches?

Issue:
Proper lubricating grease required for the QMB switches

Product Line:
QMB panelboard

Environment:
Products sold in the United States.

Cause:
Maintenance.

Resolution:
SWLUB is the proper lubricant for the switch blades themselves, and PJC7201 is for the plug on jaws that plug onto the bus bars. Do not use one for the other.