Issue:
Where does the Vn connection get made on the P and R-frame and Masterpact neutral current transformers?
Product Line:
Circuit Breakers
Resolution:
The Vn connection is used with a Power trip unit (5.0P or 6.0P) or Harmonic (5.0H or 6.0H) trip unit because they monitor voltage. On a Masterpact breaker, wire Vn from the NCT to Vn on the breaker. On a P or R frame breaker, connect the Vn wire from the breaker to Vn on the NCT.
The Vn connection is not used with ammeter trip unit (5.0A or 6.0A) because it only monitors current and not voltage.
Where does the Vn connection get made on the P and R-frame and Masterpact neutral current transformers?
Product Line:
Circuit Breakers
Resolution:
The Vn connection is used with a Power trip unit (5.0P or 6.0P) or Harmonic (5.0H or 6.0H) trip unit because they monitor voltage. On a Masterpact breaker, wire Vn from the NCT to Vn on the breaker. On a P or R frame breaker, connect the Vn wire from the breaker to Vn on the NCT.
The Vn connection is not used with ammeter trip unit (5.0A or 6.0A) because it only monitors current and not voltage.