Is there a walking beam interlock for Powerpact H, J, and L frame breakers?
Product Line:
Circuit Breakers
Resolution:
The walking beam interlock is not an option with Powerpact breakers. It was only offered with the legacy FA, KA, LA, etc. type breakers. The Powerpact design does not permit a walking beam configuration.
For Powerpact H, J, and L, we can offer mechanical interlocking with S32621 for rotary handles and S32614 for toggle handle breakers. The rotary interlock functions much like the walking beam, but the toggle interlock requires turning a breaker off and manually moving a slide to block one handle and enable operation of the other.
See attached instruction bulletins.
Circuit Breakers
Resolution:
The walking beam interlock is not an option with Powerpact breakers. It was only offered with the legacy FA, KA, LA, etc. type breakers. The Powerpact design does not permit a walking beam configuration.
For Powerpact H, J, and L, we can offer mechanical interlocking with S32621 for rotary handles and S32614 for toggle handle breakers. The rotary interlock functions much like the walking beam, but the toggle interlock requires turning a breaker off and manually moving a slide to block one handle and enable operation of the other.
See attached instruction bulletins.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.