What fuse type is required for the 8538SC*12/13/14/22/23/24/62/65 combination starter?
Issue:
Fuse Type required for Combination starter size 1.
Product Line:
NEMA and Definite Purpose Contactors
Environment:
8538 Fusible combination starters
Resolution:
This device is configured from the factory to accept Class H, J, K or R fuse types. However, this device is not supplied with Class R rejection pins. If Class J type (applications above 250 volt) fuses are used it will require re-positioning of the fuse base.
Fuse Type required for Combination starter size 1.
Product Line:
NEMA and Definite Purpose Contactors
Environment:
8538 Fusible combination starters
Resolution:
This device is configured from the factory to accept Class H, J, K or R fuse types. However, this device is not supplied with Class R rejection pins. If Class J type (applications above 250 volt) fuses are used it will require re-positioning of the fuse base.
Released for: Schneider Electric USA