Do the Powerpact H and J motor circuit protectors have an instantaneous dial adjustment?

Issue:
Is an Instantaneous dial adjustment present in Powerpact H and J Motor Circuit Protectors?

Product Line:
Molded Case Circuit Breakers

Resolution:
Yes, there is a full load amp setting adjustment and an instantaneous trip point setting adjustment. The dials are detented and allow the protector to be set to specific trip values within a typical accuracy range of +/- 5%.