How can we help you today?
What is the lug wire range for an 800 amp main lugs I-Line panel?
Issue:
What are the conductor sizes for an 800A MLO I-line panel?
Product Line:
Panels
Environment:
I-line Products sold and used in the United States
Cause:
Product Features
Resolution:
The lugs on this panel will accept 4-#3/0 to 750kcmil Al/Cu per phase and neutral. However, the conductors are limited to 3-#3/0 to 500kcmil Al/Cu per phase and neutral to conform to UL/CSA wire bending space.
What are the conductor sizes for an 800A MLO I-line panel?
Product Line:
Panels
Environment:
I-line Products sold and used in the United States
Cause:
Product Features
Resolution:
The lugs on this panel will accept 4-#3/0 to 750kcmil Al/Cu per phase and neutral. However, the conductors are limited to 3-#3/0 to 500kcmil Al/Cu per phase and neutral to conform to UL/CSA wire bending space.
Released for: Schneider Electric USA