An HJA breaker is not fitting properly in an older I-line panel. Is there a difference in the way the HJA installs compared to the older F and K frame breakers?

Issue:
Differences in the way the HJA installs compared to the older F and K frame breakers

Product Line:
Panelboards.

Environment:
Products sold and used in the United States

Cause:
Installation / Setup

Resolution:
The screw on the off end of an H frame circuit breaker (mounted in an I-Line panel) needs to be affixed to a slot on the back pan, not a round hole. This differs from the earlier F and K frame breakers which used the round hole for the mounting screw.