Please provide documentation that our switchgear doors are adequately grounded without bonding jumpers.
Issue:
Documentation on switchgear doors are adequately grounded without bonding jumpers
Product Line:
Switchgears
Environment:
Products sold and used in the United States
Cause:
Product Features
Resolution:
Per Mike Orosz on 12/03/08 - ``The ANSI C37 standard does not require bonding wire between door, removable panels etc. to the frame if it is tested and proven that the grounding is adequate. Square D switchgear was tested without the bonding wires up to 50kA SCI level. The frame, doors and panels were OK, the grounding was good. Square D considers the hinges as the grounding path.``
Documentation on switchgear doors are adequately grounded without bonding jumpers
Product Line:
Switchgears
Environment:
Products sold and used in the United States
Cause:
Product Features
Resolution:
Per Mike Orosz on 12/03/08 - ``The ANSI C37 standard does not require bonding wire between door, removable panels etc. to the frame if it is tested and proven that the grounding is adequate. Square D switchgear was tested without the bonding wires up to 50kA SCI level. The frame, doors and panels were OK, the grounding was good. Square D considers the hinges as the grounding path.``
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.