How can we help you today?

What is the replacement for the 9038BG7?

Issue:
What is the current offer for 9038BG7?

Product Line:
Pressure Switches

Environment:
Class 9038 Type B Mechanical Alternator

Resolution:
The 9038BG7 was replaced by the 9038BG21 but now it is not obsolete. Therefore there is no direct replacement.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings