How can we help you today?

What is the maximum wire size for 9013 Type F or G pressure switches?

Issue:
9013 largest wire size

Product Line:
Pressure switches

Environment:
Class 9013 Type F and Type G pressure swtches

Cause:
What is the maximum wire size for 9013F pressure switches?

Resolution:
The power terminals and ground terminal are suitable for a single #10 AWG copper (CU) wire.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings