How does a Q1150AN neutral lug mount on an NQ neutral assembly or ground bar?
Issue:
How can the Q1150AN be installed on an NQ neutral assembly or ground bar?
Product Line:
Panelboards
Environment:
NQ Panelboard
Cause:
Installation
Resolution:
For mounting on neutral bar assembly:
1. Remove three adjacent wire binding screws from neutral bar.
2. Mount connector plate to neutral bar using two 1/4-28 screws. Torque screws to 35 IN lbs.
3. Mount neutral branch lug on connector plate with #12-24 pan head screw. Torque screw to 50 IN lbs.
4. Install #1 - #4/0 AWG AL/CU wire and secure wire with wire binding screw. Torque screw to 150 IN lbs.
NOTE: The connector plate, branch lug, wire binding screw and mounting screws are included in the Q1150AN kit. Refer to Instruction Sheet #48040-220-06.
How can the Q1150AN be installed on an NQ neutral assembly or ground bar?
Product Line:
Panelboards
Environment:
NQ Panelboard
Cause:
Installation
Resolution:
For mounting on neutral bar assembly:
1. Remove three adjacent wire binding screws from neutral bar.
2. Mount connector plate to neutral bar using two 1/4-28 screws. Torque screws to 35 IN lbs.
3. Mount neutral branch lug on connector plate with #12-24 pan head screw. Torque screw to 50 IN lbs.
4. Install #1 - #4/0 AWG AL/CU wire and secure wire with wire binding screw. Torque screw to 150 IN lbs.
NOTE: The connector plate, branch lug, wire binding screw and mounting screws are included in the Q1150AN kit. Refer to Instruction Sheet #48040-220-06.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.