Can a 100% rated HDL or JDL circuit breaker be installed into a JD250S enclosure?

Issue:
Application

Product Line:
Circuit Breaker Enclosures

Resolution:
This enclosure has been tested and listed for use ONLY with standard rated (80%), 3p HDL or JDL breakers.
NOTE: The voltage is limited to 480 Vac maximum. The SCCR is limited to 18 kAIC 240 Vac or 480 Vac. Copper conductors (75°C) MUST be used.