Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can Schneider Panelboards be built to meet seismic standards?
Issue:
What seismic standards are Schneider Panelboards be built to ?

Product Line:
NQ NF I-Line QMB Panelboards

Environment:
Seismic Zone Appllication

Resolution:
Square D NQ, NF, I-Line and QMB panelboards meet the seismic requirements of ICBO 2000 when the following guidelines are met:

Bolt-on circuit breakers are required on NQ and NF panelboards.
Boxes must be secured to wall/structure by utilizing all mounting holes provided in box and secured with grade 2 steel bolts sized per the mounting holes.

See Web link to Data Buletin, 1640DB0802.
"The seismic provisions of the 2006 International Building Code (IBC) requires strenuous shaker table testing for panelboards. The new NQ panelboard successfully completed this testing without any structural damage, while retaining electrical continuity."

https://www.se.com/us/en/download/document/1640DB0802/



Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings