What is the part number for the fuse clips for a Model 6 MCC fusible switch feeder bucket rated 30A at 600V or 480V 3 phase?
Issue:
Fuse clips for a M6 MCC fusible feeder 30A, 600V or 480V
Product Line:
Model 6 Motor Control Center
Environment:
Products sold in North America
Resolution:
For a class R application order Qty 3 of part number 153014 (Line side fuse clip) and qty 3 of part number- 40512-691-50 (load side class R fuse clip assembly)
For a Class H application order Qty 6 of part number 153014 (line and load side fuse clips)
For a Class J application order Qty 6 of part number 3001505150 (line and load side fuse clips)
Fuse clips for a M6 MCC fusible feeder 30A, 600V or 480V
Product Line:
Model 6 Motor Control Center
Environment:
Products sold in North America
Resolution:
For a class R application order Qty 3 of part number 153014 (Line side fuse clip) and qty 3 of part number- 40512-691-50 (load side class R fuse clip assembly)
For a Class H application order Qty 6 of part number 153014 (line and load side fuse clips)
For a Class J application order Qty 6 of part number 3001505150 (line and load side fuse clips)
Released for: Schneider Electric USA