Can a 480Y/277V rated EMA SPD be used on a 120/208V system?
Issue:
Is it possible to use a 480Y/277V rated EMA SPD on a 120/208V system?
Product Line:
TVSS/ SPD
Environment:
Application
Cause:
Verification
Resolution:
No, the clamping voltage of the EMA SPD would be too high to be effective. Using a SPD designed for 480Y/277V on a 208Y/120V system would not allow it to provide adequate protection. A 208/120V SPD would start conducting at 150V from L-G and L-N, whereas a 480/277V SPD would start conducting at 320V from L-G and L-N. Additionally, placing a 480/277V SPD into a 208/120V system would cause issues with the diagnostics due to insufficient voltage for the diagnostic circuit.
Is it possible to use a 480Y/277V rated EMA SPD on a 120/208V system?
Product Line:
TVSS/ SPD
Environment:
Application
Cause:
Verification
Resolution:
No, the clamping voltage of the EMA SPD would be too high to be effective. Using a SPD designed for 480Y/277V on a 208Y/120V system would not allow it to provide adequate protection. A 208/120V SPD would start conducting at 150V from L-G and L-N, whereas a 480/277V SPD would start conducting at 320V from L-G and L-N. Additionally, placing a 480/277V SPD into a 208/120V system would cause issues with the diagnostics due to insufficient voltage for the diagnostic circuit.
Released for: Schneider Electric USA
Explore more
Range:
Product:
Explore more
Range:
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.