Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Will a PowerPacT H frame with a GFM150HD ground fault module fit into an HCN I-Line panel?
Issue:
GFM150HD ground fault module into an HCN I-Line Panel

Product Line:
Panelboards

Resolution:
No. You must use at least an HCP type panel to fit the GFM module into it, since the module adds 4.85" to the length of the breaker.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings