How can we help you today?

The fan operation for the Back UPS XS/ NS / RS ""G"" / ""GI" models.

Issue:

What is the fan operation of the Back UPS XS/ NS / RS ""G"" / ""GI"" models?

Product Line:

Back-UPS Models BX / BN and BR

Environment:

Effective manufacturing week 42 of 2010, For the BX/BN/BR ""G"" / ""GI"" models of Back UPS, the fan will operate only during AVR Boost operation.

Cause / Resolution:
AVR Boost (88~105vac) Percentage Loading Fan Duty Cycle
0% 50%
40% 62.5%
60% 75%
100% Always On



Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings