How can we help you today?
What is a replacement copper lug for a main lugs HCN I-Line panel ?
Issue:
Is there a replacement copper lug for a main lugs HCN I-Line panel ?
Product Line:
Panelboards
Environment:
I-Line Power Distribution Panelboard - HCN
Resolution:
Use a 80048-002-01 copper lug for 2 - #2 thru 600kcmil
Below is the terminal data for all of the panelboards found on page 9-40 in Digest 177, Section 9. Table 9.187 shows the terminal data for the phase and neutral lugs on main lug panels. Table 9.188 shows the standard terminal for main breaker available for ILINE panelboard (please see page 7-41 of Digest 177, Section 7 or page 3-28 of the Supplemental Digest 177, Section 3 for other terminal options for given breakers).
Standard Mechanical Lugs—Main Lugs
| Amp | Lug Wire Range | Wire Range Wire Bending Space per NEC Table 373-6 |
| 225 A | one #6–300 kcmil Al or Cu | one #6–300 kcmil Al or Cu |
| 400 A | two #2–600 kcmil Al or Cu | one #2–600 kcmil Al or Cu |
| 600 A | two #2–600 kcmil Al or Cu | two #2–500 kcmil Al or Cu |
| 800 A | (4) 3/0–750 kcmil Al or Cu | (3) 3/0–500 kcmil Al or Cu |
| 1200 A | (4) 3/0–750 kcmil Al or Cu | (4) 3/0–500 kcmil Al or Cu |
Standard Mechanical Lugs—Main Circuit Breaker
| Amp | Circuit Breaker Type | Lug Wire Range | Wire Range Wire Bending Space per NEC Table 373-6 |
| 100 A | FA, FH, FI | one #14-1/0 Al or Cu | one #14-1/0 Al or Cu |
| 150 A | HD, HG, HJ, HL | one #14-3/0 Al or Cu | one #14-3/0 Al or Cu |
| 225 A | KI | one #4-300 kcmil Al or Cu | one #4-300 kcmil Al or Cu |
| 250 A | JD, JG, JJ, JL | one #1/0-#4/0 Al or Cu | one #1/0-300 kcmil Al or Cu |
| LX, LXI, LE | two #1-350 kcmil Al or Cu | two #1-350 kcmil Al or Cu | |
| 400 A | LA, LH | one #1-600 or two #1-250 kcmil Al or Cu | one #1-600 kcmil Al or Cu |
| 600 A | LC, LI, LX, LXI, LE | two 4/0-500kcmil Al or Cu | two 4/0-500kcmil Al or Cu |
| 800 A | MG, MJ, PG, PJ, PL | three 3/0-500 kcmil Al or Cu | three 3/0-500 kcmil Al or Cu |
| 1200 A | PG, PJ, PL, RGC, RJC, RLC | four 3/0-500 kcmil Al or Cu | four 3/0-500 kcmil Al or Cu |
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.