What are the assignments for the output relays on an ATV212 ?
Issue:
ATV212 output relays assignments.
Product Line:
ATV212
Environment:
Output relays
Cause:
n/a
Resolution:
FLA, FLB, FLC are the terminals for a single pole, double throw (Form C) relay and the default assignment is ``inversion of fault relay``. Off = drive faulted, On = no drive fault. Parameter F132 can be used to change this relay function.
RYA, RYC are terminals for a single normally open contact (Form A) and the default setting is ``speed attained``. The relay contact closes when the hertz value assigned to F100 is reached. F100 is defaulted to 0. A common customer request is for ``drive running``. Parameter F130 can be assigned to 14 for ``drive running``.
ATV212 output relays assignments.
Product Line:
ATV212
Environment:
Output relays
Cause:
n/a
Resolution:
FLA, FLB, FLC are the terminals for a single pole, double throw (Form C) relay and the default assignment is ``inversion of fault relay``. Off = drive faulted, On = no drive fault. Parameter F132 can be used to change this relay function.
RYA, RYC are terminals for a single normally open contact (Form A) and the default setting is ``speed attained``. The relay contact closes when the hertz value assigned to F100 is reached. F100 is defaulted to 0. A common customer request is for ``drive running``. Parameter F130 can be assigned to 14 for ``drive running``.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.