How is the comms address set on a Micrologic ammeter or energy trip unit for H, J, and L frame breakers?

Issue:
How to set the comms address on a Micrologic ammeter or energy trip unit?

Product Line:
Micrologic  5.2A, 5.2E, 5.3A, 5.3E, 6.2A, 6.2E, 6.3A, 6.3E trip units

Resolution:
The comms address is set on the Modbus communication interface module (IFM) with blue dials. The IFM is external to the breaker and is mounted on a DIN rail.
This module, required for connection to the network, contains the Modbus address (1 to 99) declared by the user using the two rotary switches on the front. It automatically adapts (baud rate, parity) to the Modbus network in which it is installed. It is equipped with a lockout switch to enable or disable operations involving writing to the Micrologic trip unit, (such as reset, counter reset, setting modifications, and device opening and closing commands). There is a built-in test function to check the connections of the Modbus communication interface module with the Micrologic trip unit and front display module.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings