Powerlink G3 opt-isolator wiring diagram for Target applications

Issue:
Need wiring information for opt-isolator application with Target sites.

Note: As of March 1, 2015 all US Lighting Control products (EXCEPT Powerlink and MVP panels) will enter their obsolescence phase and will no longer be purchasable for new orders. Management of the Prosumer Business has made a strategic decision to stop the Lighting Control initiative and concentrate our effort in new businesses with higher growth potential – Connected Home, Building Control in small buildings, and Electric Vehicle solutions.

Product Line:
Powerlink G3

Environment:
Communication between Powerlink G3 panels without running 4 wire subnet with 24VDC power. Power Slave application.

Cause:
Applications were running 4 wire subnet is not possible. Only able to run communication and not 24VDC power.

Resolution:
See Wiring diagram attached.

Schneider Electric USA

Attachment(s)
Target(OptoIsolatorRevision 3).pdf [1.37 MB]