How can we help you today?

How do I compare drive configuration files with SoMove?

Issue:
SoMove files configuration comparison.

Product Line:
ATV312, ATV32, ATV320, ATV61, ATV71, ATV600, ATV900, ATS48, ATS480,ATS22

Cause:
None

Resolution:
In order to compare configurations between two drives using SoMove, both drives have to be the same model numbers and both configuration files should be saved.
1. Open one of the configurations
2. Select "Compare Configurations" from the File menu
3. Select the configuration file of the device that you want to compare
Both configuration files will be displayed on the screen.  The values highlighted are those parameters that are different.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings