What could cause an INF6 fault on the ATV32 drive?

Resolution:

  • Inspect the Drive Connector Pins

Check if any of the pins are bent on the drive where the option card plugs in.
If bent pins are found, carefully straighten them or replace the drive if necessary.

  • Swap Option Cards

Try swapping the option cards between drives.
Observe whether the issue stays with the original drive or follows the card.

If the issue follows the card: The card may be faulty.
If the issue stays with the drive: The drive may be the source of the problem.

  • Test the Drive Without an Option Card

Remove the option card and power up the drive.
If the drive faults without the card installed, a replacement drive may be required.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings