Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I calculate the energy savings when using a Constant Torque rated VFD in a Constant Torque Application?
Issue:
Information needed to determine the energy savings for a variable frequency drive (VFD) system in a constant torque application.

Product Line:
All constant torque rated Altivar Drives.

Environment:
All constant torque rated drives, All serial numbers.

Cause:
What is the percentage of energy usage reduction compared to the reduction in speed?

Resolution:
In a constant torque application, The energy used is directly proportional to the speed of the motor.   At 25% speed, 25% energy is used.  At 50% speed, 50% energy is used.  This is different than in variable torque applications where the reduction in power usage is greater than the reduction in speed.

When calculating energy consumption for constant torque applications, The percentage of motor speed is used to determine energy usage.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings