Can a 2 pole breaker be installed in a new NQ panel with a B phase high leg?

Issue:
Can a 2 pole breaker be installed in a new NQ panel with a B phase high leg?

Product Line:
NQ Panelboards

Environment:
Products sold in North America

Resolution:
Yes, a 2 pole breaker can be installed into an NQ panel with a B phase high leg, if the B phase does not have a rejection screw in its connector .

240/120V 3phase, 4wire B high leg voltage systems will only affect 1 pole branch breakers plugged into the B phase.  The voltage from B phase to Neutral is 208V; normal 1 pole voltage from A/C phases is 120V.  Connecting to B phase with 2 or 3 pole breakers is fine as long as bussed B phase available for a breaker.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings