How can we help you today?

When testing the voltage of a (typically 120V) hospital isolated power system, why am I not getting 120V to ground?

Issue:
Not getting 120V to ground when testing the voltage of a (typically 120V) hospital isolated power system

Product Line:
Hospital Isolated Power Systems

Environment:
NFPA99, NEC517.160

Cause:
Product Design

Resolution:
A hospital isolated power system is an ungrounded system, and for this reason, one should not anticipate the measured voltage between ground and either line to be 120V.
In practice, one should expect to read about 50% of the system voltage from either line to ground.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.