When do I need to test my isolated power system?

Issue:
Isolated Power System testing

Product Line:
Hospital Isolated Power Systems

Environment:
NFPA 99, NEC517.160

Resolution:
Check with the local Authority Having Jurisdiction (AHJ) for specific guidelines for your area. It is recommended that a “Periodic Testing/Maintenance Program" be instituted on the Isolated Power Systems (IPS) based on the test procedures stated in NFPA 99. This program should be implemented in the Hospital's "Utility System Management Plan" to satisfy the requirements of JCAHO’s (The Joint Commision) Environment of Care (EC.02.05.01 and EC.02.05.05). The program should include the following:
1. Date of original installation
2. Date of any enhancements and/or upgrades
3. Maintenance history of ongoing Line Isolation Monitors (LIMs) including any:
- incidents of patients harmed
- equipment failures
- repair work via work order
- preventive maintenance test data (this document)
RECOMMENDED PREVENTIVE MAINTENANCE TEST PLAN

Tier I: (Annually)
- Line-to-Ground fault simulations
-Bi-Annual for Analog LIMs
- Calibration check of LIMs
- Bi-Annual for Analog LIMs
- Verification of associated remote indicator alarms
- Receptacle retention force test.
- Electronic Report

Tier II: (Recommended every 3-5 years or after system repairs/renovations) Tier I plus
- Measurement/Calculation of individual circuit and system impedance(s) (leakage currents)
- Equipotential ground system testing
NOTE: Analog LIMs
On a monthly basis, facility personnel should depress the Line Isolation Monitor (LIM) test buttons to assure proper functionality of the audible alarms and visual indicators.
Additionally, meters should be observed for proper response and alarm Mute/Silence functions should be verified.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.