How can we help you today?
What are the replacement Neutral lugs for a NF442L6C interior ?
Issue:
Neutral lugs replacement for a NF442L6C interior
Product Line:
PTEQP - LV EQPT (IEC&NEMA)
Environment:
Maintenance replacement parts
Cause:
Lost, or replacement neutral lug replacement part number
Resolution:
The Neutral assembly uses (2) 80122-137-50 lugs and requires (4) screws , (2) for each lug , p/n is 80114-004-05
Neutral lugs replacement for a NF442L6C interior
Product Line:
PTEQP - LV EQPT (IEC&NEMA)
Environment:
Maintenance replacement parts
Cause:
Lost, or replacement neutral lug replacement part number
Resolution:
The Neutral assembly uses (2) 80122-137-50 lugs and requires (4) screws , (2) for each lug , p/n is 80114-004-05
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.