Issue:
RJ or RL Powerpact breaker is not passing primary injection testing for ground fault. New trip unit was recently installed.
Product Line:
Powerpact RJ or RL
Resolution:
Do NOT install new trip units in Compact NS1600b–3200 H interrupting rating or PowerPacT RJ/RL circuit breakers with a date code of 09011 or earlier. See A, Figure 1 of attached Micrologic special instruction bulletin 48049-160-01 for location of date code on breaker.
To resolve this issue, reinstall the older trip unit or replace the breaker.
RJ or RL Powerpact breaker is not passing primary injection testing for ground fault. New trip unit was recently installed.
Product Line:
Powerpact RJ or RL
Resolution:
Do NOT install new trip units in Compact NS1600b–3200 H interrupting rating or PowerPacT RJ/RL circuit breakers with a date code of 09011 or earlier. See A, Figure 1 of attached Micrologic special instruction bulletin 48049-160-01 for location of date code on breaker.
To resolve this issue, reinstall the older trip unit or replace the breaker.