How can we help you today?

RJ or RL PowerPacT breaker with new trip unit installed does not pass primary injection test for ground fault

Issue:
RJ or RL Powerpact breaker is not passing primary injection testing for ground fault.  New trip unit was recently installed.

Product Line:
Powerpact RJ or RL

Resolution:
Do NOT install new trip units in Compact NS1600b–3200 H interrupting rating or PowerPacT RJ/RL circuit breakers with a date code of 09011 or earlier. See A, Figure 1 of attached Micrologic special instruction bulletin 48049-160-01 for location of date code on breaker.

To resolve this issue, reinstall the older trip unit or replace the breaker.

Schneider Electric USA

Attachment(s)
Micrologic Special Instructions.pdf [679.86 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings