How do I configure the ATV12 AI1 input for a 4–20 mA signal?

Resolution:
To configure AI1 for a 4–20 mA signal:

  1. Navigate to: ConF → FULL → I/O → AI1
  2. Set AI1t (AI1 Type) to 0A for current input.
  3. The current input range defaults to 4–20 mA.
  4. If a different current range is required, adjust:
    • CrL1: AI1 minimum current
    • CrH1: AI1 maximum current

After these settings are applied, AI1 can be used as a 4–20 mA analog reference.