Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the life expectancy of molded case circuit breakers?
Product Line:
MCCB

Resolution:
Life expectancy for molded case circuit breakers in the industry is generally expected to be about 30 years, given favorable environment and regular maintenance. Required maintenance, especially for older breakers, includes annual exercising—OFF, ON, TRIP, RESET, ON. This will help to ensure that the mechanism remains operable. Conditions of service, including number of on-off cycles, number of load operations, overloads, short circuits, environmental conditions, and maintenance may affect the time of useful service.

See the attached maintenance guides for more information.

Schneider Electric USA

Attachment(s)
Field Test and Maint 0600IB1201 2013.pdf [2.38 MB]
Field Test and Maint 0613IB1202 2015.pdf [5.21 MB]
Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings