What is the mounting height for Square D I-Line circuit breakers and subfeed lug kits?

Issue:
What is the mounting height (in inches) for the FY, FA, FH, SL-100, FI, HDA, HGA, HJA, HLA, QBA, QDA, QGA, QJA, JDA, JGA, JJA, JLA, LDA LGA LJA LLA LRA KI, SL250, LA, LH, SL400, LC, LI, LXI, MGA, MJA, MA, MH, SL800, PGA, PJA, PLA, RGA, RJA, AND RLA in an I-LINE panel?

Product Line:
I-LINE Breakers

Resolution:
See the table below for the mounting height for various breakers:

Frame Poles(in)
FD, FG, FJ11.5
FY, FA, FH, BD, BG, BJ, BK1
FA, FH, BD, BG, BJ23
FD, FG, FJ (no accessories)2, 3
HD, HG2
QB, QD, QG, QJ, Q22
FA, FH, SL100, BD, BG, BJ34.5
FC, FI2, 3
FD, FG, FJ (with accessories)2, 3
HD, HG3
HJ, HL, HR, QO Distribution Panels (HQO part numbers)2, 3
QB, QD, QG, QJ, Q23
JD, JG, JJ, JL, JR, KA, KH, KC, KI, IK, SL2502, 34.5
LA, LH, Q4, SL400, Smart Cell (ICW part numbers)6
LD, LG, LJ, LL, LR
LC, LI, LX, LXI, LE7.5
MG, MJ, MA, MH, MX, ME9
PG, PJ, PL
SL800, SL800M5, SL1200P5, SL1200P6, SL1200P7, S33931
IL12
RG, RJ, RL, RGC, RJC, RLC, S33930, NA, NC, NX, NE15


From page 9-34 in Section 9, Digest 177

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.