Issue:
Do the Powerpact H and J frame breakers have interchangeable thermal-magnetic trip units?
Product Line:
Molded Case Circuit Breaker
Environment:
Powerpact H- and J- Frame Circuit Breakers
Resolution:
Trip units can be changed on Powerpact H, J, and L frame breakers with the T or R suffix only. Trip units without the T or R suffix cannot be changed.
Circuit breakers with interchangeable trip units are marked Line and Load and CANNOT be reverse fed.
Note that interchangeable trip units are not possible on I-Line H and J frame breakers or on 2 pole breakers.
*Available trip units for Powerpact H 60A frame
15 A HT3015
20 A HT3020
25 A HT3025
30 A HT3030
35 A HT3035
40 A HT3040
45 A HT3045
50 A HT3050
60 A HT3060
*Available trip units for Powerpact H 100 and 150A frames
70 A HT3070
80 A HT3080
90 A HT3090
100 A HT3100
110 A HT3110
125 A HT3125
150 A HT3150
*Available trip units for Powerpact J 250A frame
150 A JT3150
175 A JT3175
200 A JT3200
225 A JT3225
250 A JT3250
Released for:Schneider Electric USA