Are the Powerpact H, J, and L frame breaker with field interchangeable trip units available in fully rated or 100% rated?

Issue:
100% rating for Powerpact H J L with interchangeable trip units

Product Lines:
Circuit Breakers

Resolution:
Yes, the catalog number for the 80% rated breaker has “T” in the 9th character space.
The catalog number for a 100% rated breaker uses “R” in the 9th character place. For example, HDL36015T or HDL36015R or LGL36400TU31X or LGL36400RU31X.
100% rated H- and J-frame circuit breakers have copper lugs and can only be used with copper wire.