How do you set up preset speeds on the ATV32 drives?
Resolution:
ConF menu enter
FULL menu enter
FUn menu enter
PSS menu enter
PS2= 2 preset speeds assign to your logic input
PS4= 4 preset speeds assign to your logic input
PS8= 8 preset speeds assign to your logic input
PS16= 16 preset speeds assign to your logic input
Preset speed values are SP2 thru SP16 in Hz.
Example: 3 preset speeds you will need to assign 2 logic inputs.
2 preset speeds = LI4
4 preset speeds = LI5
Logic will be as follows
LI4=0 LI5=0 Drive runs at low speed for follows your analog input.
LI4=1 LI5=0 Drive runs at speed 2
LI4=0 LI5=1 Drive runs at speed 3
LI4=1 LI5=1 Drive runs at speed 4
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.