Issue:
What is the torque requirement for a PK5GTA equipment ground kit?
Product Line:
Ground Bars
Resolution:
#14 - #10 Cu, #12 - #10 Al = 20 lb-in.
#8 Cu/Al = 25 lb-in.
#6 - #4 Cu/Al = 35 lb-in.
Two #14 - #12 Cu, Two #12 - #10 Al = 25 lb-in.
What is the torque requirement for a PK5GTA equipment ground kit?
Product Line:
Ground Bars
Resolution:
#14 - #10 Cu, #12 - #10 Al = 20 lb-in.
#8 Cu/Al = 25 lb-in.
#6 - #4 Cu/Al = 35 lb-in.
Two #14 - #12 Cu, Two #12 - #10 Al = 25 lb-in.
Released for:Schneider Electric USA