What is the tripping current for a Multi 9 GFP?
Issue:
What is the tripping current for a Multi 9 GFP Ground Fault Protector?
Product Line:
Circuit breakers
Resolution:
Tripping currents are as follows:
GFP30 Must trip beyond 29.9 mA; must not trip below 22.1 mA
GFP100 Must trip beyond 98.9 mA; must not trip below 73.1 mA
GFP300 Must trip beyond 299 mA; must not trip below 221 mA
What is the tripping current for a Multi 9 GFP Ground Fault Protector?
Product Line:
Circuit breakers
Resolution:
Tripping currents are as follows:
GFP30 Must trip beyond 29.9 mA; must not trip below 22.1 mA
GFP100 Must trip beyond 98.9 mA; must not trip below 73.1 mA
GFP300 Must trip beyond 299 mA; must not trip below 221 mA