{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
How often should the NetShelter CX dust filters be cleaned?
Issue:
NetShelter CX owners need to know how often to clean the dust filters.

Product Line:
NetShelter CX

Environment:
All versions and serial ranges.

Cause:
A dirty dust filter can reduce airflow and cause increased heat in the cabinet.

Resolution:
In a normal office environment the dust filter should be cleaned every 12 weeks.
The scale of cleaning can slide all the way up to 'daily' in a dusty environment. In those cases we recommend customers buy a spare set of dust filters, to always have a clean set on hand.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: