Class 1, Division 2 use for 9001K and 9001SK operators
Issue:
Under what conditions can 9001K or 9001SK operators be used in Class 1 Division 2 applications?
Product Line:
9001K and 9001SK operators
Environment:
US Product
Cause:
Class 1 Division 2 applications do not necessitate the need for NEMA 7 or NEMA 9 control stations
Resolution:
9001K and 9001SK operators can be used for Class 1 Divsion 2 Groups A, B, C, D applications so long as all of the following restrictions are observed:
1) Only logic (9001KA40) or power (9001KA50) reed contact blocks are used
2) All type K or SK illuminated operators are UL approved for use in Class 1 Division 2 areas - push to test single lamp pilot lights require Y243 form code.
3) Type KX illuminated operators do not use four lamp modules or 2 lamp modules other than the transformer type.
4) The operators are mounted in any NEMA 4 or NEMA 13 enclosure
5) Potentiometers are not used
Under what conditions can 9001K or 9001SK operators be used in Class 1 Division 2 applications?
Product Line:
9001K and 9001SK operators
Environment:
US Product
Cause:
Class 1 Division 2 applications do not necessitate the need for NEMA 7 or NEMA 9 control stations
Resolution:
9001K and 9001SK operators can be used for Class 1 Divsion 2 Groups A, B, C, D applications so long as all of the following restrictions are observed:
1) Only logic (9001KA40) or power (9001KA50) reed contact blocks are used
2) All type K or SK illuminated operators are UL approved for use in Class 1 Division 2 areas - push to test single lamp pilot lights require Y243 form code.
3) Type KX illuminated operators do not use four lamp modules or 2 lamp modules other than the transformer type.
4) The operators are mounted in any NEMA 4 or NEMA 13 enclosure
5) Potentiometers are not used
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.