Will the ATS22 Display Power Up with Only Control Voltage Applied?

Resolution:

Yes. The ATS22 display should power up when the proper control voltage is applied, even if line power is not present.

If the display does not illuminate, perform the following checks:

  1. Disconnect any remote HMI that may be connected to the soft starter.
  2. Measure the control voltage at terminals CL1 and CL2.
  3. Verify that the measured voltage matches the requirements for your ATS22 model:
    • ATS22...S6 and ATS22...Q models: approximately 230 VAC
    • ATS22...S6U models: approximately 110 VAC

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings