Can the ATV312 Drive switch from local keypad control to remote terminal control by pressing and holding the mode button?
Issue:
ATV312, local mode to remote mode.
Resolution:
The drive can be changed from remote (Terminal) mode to local (Keypad) mode by pressing and holding the mode (Mod) button for 3 seconds.
However, when returning to remote from local requires the drive to be reset to factory defaults using the FCS parameter in the drC menu.
Consult the ATV312 Programming manual for details.
https://www.se.com/ww/en/download/document/BBV46385/
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)