Why am I getting an error: "The Main Drive or Secondary Drive is full. Runtime cannot execute" on the Magelis when installing with a USB stick?
Issue:
"The Main Drive or Secondary Drive is full. Runtime cannot execute" appears on the Magelis when trying to install an application.
Product Line:
XBTGC/GH/GK/GT, HMIGTO/STO/STU
Resolution:
This error message can appear when the Magelis does not have a CF card/SD card installed. To confirm, goto the Data Locations in Vijeo Designer and check if you have "User Application", "Data Files / Forms", "Recipes", or "Web Server" set for Secondary Drive. If yes, then this means that you need to have a CF/SD card (depending on unit) installed in the unit. Once you add a CF/SD card, reloading from the USB stick complete successfully. Alternatively, you may set the data locations to use Main drive if you do not have a secondary or optional drive.
"The Main Drive or Secondary Drive is full. Runtime cannot execute" appears on the Magelis when trying to install an application.
Product Line:
XBTGC/GH/GK/GT, HMIGTO/STO/STU
Resolution:
This error message can appear when the Magelis does not have a CF card/SD card installed. To confirm, goto the Data Locations in Vijeo Designer and check if you have "User Application", "Data Files / Forms", "Recipes", or "Web Server" set for Secondary Drive. If yes, then this means that you need to have a CF/SD card (depending on unit) installed in the unit. Once you add a CF/SD card, reloading from the USB stick complete successfully. Alternatively, you may set the data locations to use Main drive if you do not have a secondary or optional drive.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.