Issue:
Is there an optional lug kit for a 400A main lug NF panelboard that accepts (2) - 500 MCM conductors?
Product Line:
NF panelboards sold and supported in the USA.
Environment:
Application
Cause:
Selection/product features
Resolution:
There is a compression lug kit, NFALV4, that will accept (2) 2/0 - 500 mcm per Digest 177.
Is there an optional lug kit for a 400A main lug NF panelboard that accepts (2) - 500 MCM conductors?
Product Line:
NF panelboards sold and supported in the USA.
Environment:
Application
Cause:
Selection/product features
Resolution:
There is a compression lug kit, NFALV4, that will accept (2) 2/0 - 500 mcm per Digest 177.
Released for: Schneider Electric USA