Why does an ATV312 only show Ref and Sup menus?


The drive menus may be intentionally locked.

Note that the menus are unlocked per factory default.  If the menu is locked then someone has set a password in the drive to prevent unauthorized access to the menus.  This password is needed to unlock the drive per the following steps:

Go to SUP menu and press enter.

Navigate to parameter COd and press enter.
If COd is set to ON the drive has been locked.

To temporarily unlock the drive you have to change the COd parameter to the password and press ENT.
This will unlock the drive until the power is cycled to the drive.

To permanently unlock the drive you must set the COd parameter to OFF after entering the password.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings