What is the torque spec. for attaching the 800A main lugs on an I line HCP panel bus?
Issue:
Tightening torque for lugs
Product Line:
Panelboards
Environment:
I-Line HCP
Cause:
Installation and Maintenance
Resolution:
The nut that holds the main lug on the connector should be tightened to 50 ft-lbs.
Tightening torque for lugs
Product Line:
Panelboards
Environment:
I-Line HCP
Cause:
Installation and Maintenance
Resolution:
The nut that holds the main lug on the connector should be tightened to 50 ft-lbs.