Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can ATV312 drive be programmed to have a 3-contactor bypass?

Issue:
Programming for 3-contactor bypass on an ATV312

Product Line:
ALTIVAR 312, ATV312

Environment:
All

Cause:
Control design

Resolution:
ATV312 is not available as an enclosed product with bypass feature.  However, the drive can be incorporated into a 3 contactor bypass design.
The Isolation (IC) and Bypass (BC) contactors are controlled by an external control circuit.  The ATV312 will control the Drive Output contactor (DOC) with an output relay assigned  for RUN status.  Then use an DOC aux contact for a run permissive input to the VFD.
An example wiring diagram is attached.

Schneider Electric USA

Attachment(s)
VFD eg 3 contactor bypass.pdf [164.8 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings